• Smart FACTORY的Smart POWER Infra PYRAMID

  • Smart POWER Infra using of Smart FACTORY[:Battery UPS + No-Battery TSP®]

    - By using the fast charge - discharge ultra-capacitor having over 10 years lifetime, the momentary voltage sag compensator
    - having 1 second duration of sag compensation with no maintenance
    - will be applied along with On-Line UPS used for 30 minutes of outage depending on the loads’ electric al feature and how critical the target loads are.
  • Smart POWER LAYER of Smart FACTORY

  • Smart POWER Vaccine® : TSP® (The Second POWER)

  • 自动化设备的瞬间电压补偿装置新技术标准
    Smart POWER Vaccine®: TSP®(The Second POWER)


  • Smart POWER Vaccine® : TSP®(The Second POWER)

  • 半导体工厂应用事例
    Smart POWER Vaccine® : TSP®(The Second POWER)


  • 半导体Foundry工厂的瞬间电压下降事故补偿成功事例
    Smart POWER Vaccine® : TSP®(The Second POWER)


    JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Total
    2005 V-sag 发生次数 - - 1 2 2 9 3 2 3 - 3 25
    Drop率 / Drop Time 11.8%
    73ms
    12.90%
    87ms
    17.70%
    53ms
    39.60%
    110ms
    50.90%
    180ms
    27.70%
    90ms
    77%
    213ms
    -
    -
    19.50%
    200ms
    -
    -
    Down Time[Hr] - - 24 153 96 456 1,054 681 1,609 - 188 - 4,261
    设备 数量(台) - - 1 13 4 129 277 181 173 - 19 - 797
    2006 V-sag 发生次数 - - - 2 3 5 6 3 - - 2 1 22
    Drop率 / Drop Time 31.80%
    120ms
    25.60%
    120ms
    27.80%
    95ms
    38.30%
    250ms
    49.70%
    115ms
    -
    -
    12.70%
    60ms
    13.00%
    95ms
    Down Time[Hr] - - - 8 - 21 25 70 - - - - 124
    设备 数量(台) - - - 7 - 6 11 28 - - - - 52
    改善效果[Hr] - - -24 -145 -96 -435 -1,029 -611 -1,609 - -188 - -4,137

    - 与2005年相比, 通过2006年V-Sag补偿对策的树立来比较设备Down率, 从而得出改善效果。